Medical Waste Incinerator, 100 to 120 Kg/hr. Supply, delivery, installation and commissioning of a medical waste incinerator suitable for disposal of Medical, General and Pathological waste in a safe and clean environment. The unit shall consist of two chambers and operate on the principal of controlled air and temperature. The unit shall consist a particulate remover (scrubbers) as stipulated in waste management regulations, 2006 (Legal notice NO. 121 of 29th September, 2006). The Unit shall be fully automatic and controlled by an automatic electronic controlled system except loading system which shall be manual. The unit shall be capable of incinerating between 100 to 120 kg of solid medical waste per hour. It shall be constructed from mild or aluminized steel lined with refractory material.For incineration, general and pathological

100 �C 120 kg/h burn rate
Two combustion chambers type; primary and Secondary, controlled/forced combustion air type with a flue gas emission scrubbing unit
Minimum 8 hours daily
From 850 0C to 1200 0C, Automatic controlled.Constructed from heavy duty mild or aluminized steel
Or equal and approved equivalent
Refractory material lining similar or equal to calcium
Silicate and hot face combination of heavy duty brickwork
Fixed hearth type complete with gratings, concave bottom and charging door, lined with refractory material.Provided, for removing resultant bottom ash leftovers from the Primary chamber
Provided
Manual loading of waste
Fully automatic, with fuel, temperature and speed controls with ignition system flame detector Air fan Complete with safety features, flame failure Diesel fired fuel injector type
Flange mounted
Provided. 3 phase for supplying excess combustion air through the distribution system with speed control system
Minimum exit 850 0C
To be provided with protective glass type.Constructed from heavy duty mild or aluminized steel or equal and approved equivalent
Refractory material lining
Above 850 0C, controlled electronically
> 2 second at minimum 850 0C
Provided,
Diesel fired,
Fully automatic, with fuel, temperature and speed controls
With ignition system
Flame detector
Air fan
Complete with safety features, flame failure
Diesel fired fuel injector type
Flange mounted
Provided, Venturi type, for cooling the flue gases
Provided for supplying combustion and creating a
negative drift and turbulences with variable speed control
Maximum 1600 0C
Fully automatic with microprocessor based control
unit (PLC) automating all operations of the incinerator
Capable of monitoring all incinerator parameters
With large LCD or similar for display of all progress
Parameters i.e. temperature of primary and second chambers , turbulence and time
With status lamp
With user of defined and differed programmed operating cycles for different type of loads/conditions
With safety interlocks, display of errors and visible and audio alarms.
System for continuous emission monitoring